 |

|
 |
 |
| Article
- Installation audit for Soporcel |
|
 |

Date: July 2007
In this article I want to enlighten you with what goes on during
a PROFIBUS installation audit. As an example I will take the
paper-mill Soporcel in Portugal (Europe) which we audited some
time ago. Soporcel has an enormous new recovery boiler which
is required for the paper fabrication process. This project
was a mutual cooperation of automation companies all over the
world. For PROFIBUS this was an important reference project,
because it proofs the acceptation of bus technology in pulp-
and paper applications. PROFIBUS was already used for pre-processing,
but never in such a large primary process.
Summary of equipment
- 5 Honeywell DCS systems
- 147 DP slaves (Siemens-ET200M/Simocode, Auma-actuators and ABB-drives)
- 470 PA slaves (E+H and Siemens)
- 58 HART instruments, coupled through I/O cards.
The companies who were responsible for the engineering, panel building and installation,
started with a training course at PROCENTEC in The Netherlands
for a week and used the acquired knowledge to do the project.
After everything was programmed and installed, it was PROCENTEC's
task to audit the installation. Two engineers went to the site
and inspected the schematics first to get an impression about
the installation. They split up the work and went with 2 teams
of engineers into the field to inspect/measure the installation.
Timing was crucial so the use of proper tools was very important.
With the ProfiTrace Analyzer, oscilloscope and the PA Probe
more than 470 PA instruments were commissioned in less than
2 days and these tools brought a lot of hidden problems to
the
surface:
1) Address swap
The addresses of instruments of the same type
have been swapped. This means the wrong process value enters/leaves
the control system. This is very difficult to detect. You can
only see it when an instrument is powered down and you check
in ProfiTrace which address "falls-out".
2) Double addresses
Two instruments accidentally had the same address and because
of this they cannot communicate. With ProfiTrace this is easy
to detect. The client has to decide what the correct address
should be.
3) Instruments with a damaged bus interface
Several
instruments had damaged electronics which were constantly transmitting
corrupted signals. This had effect on the entire segment. When
the instruments were replaced everything was OK again. With
ProfiTrace and the oscilloscope this was easy to detect.
4)
Contact problems
A couple of connectors did make proper contact
because the screws have not been tightened sufficiently. This
was easily detected with ProfiTrace. The oscilloscope was used
to pinpoint the exact location.
5) Too many termination
The
termination switch of some devices was accidentally set to
ON. Some segments had 6 or more terminations active, which
corrupted the signals. This could only be detected with the
oscilloscope.
All of the deviations we have detected at this
site have to do with cabling. This is most of the time the
same issue. All issues were solved directly by the team of
engineers that went with us and the installation is now running
on 100% with full availability of all instruments. After this
successful project, more plants that belong to this organization
will be automated with PROFIBUS.
 |
|
Copyright ©2011 PROCENTEC. All rights reserved.
- info@procentec.com -
+31-174-671800 - Update:
23 December, 2011
 |
 |